Grounding instructions for cabinets and chassis 133
Figure 57
NTBK80 grounding block
6
Connect the grounding block to the ground bus in the AC power
service panel, using #6 AWG wire. See Table 20 "Region-specific
grounding wire requirements" (page 129) for region-specific
grounding requirements.
DANGER
DANGER OF ELECTRIC SHOCK
A qualified technician or electrician must make the
connection in the AC power service panel.
7
Place a DO NOT DISCONNECT tag on the ground wire at the
service panel.
8
Test the ground.
—End—
Nortel Communication Server 1000
Communication Server 1000M and Meridian 1 Small System Installation and Commissioning
NN43011-310 01.04 Standard
Release 5.0 13 May 2008
Copyright © 2008, Nortel Networks
.